《带负荷测试记录.docx》由会员分享,可在线阅读,更多相关《带负荷测试记录.docx(14页珍藏版)》请在第一文库网上搜索。
1、紫城500千伏变电站新建工程二次设备试验报告带负荷试验报告国网黑龙江省送变电工程有限公司二。二O年十二月二十七日第一次核相:紫青1号线、2号主变50OkV侧、500kV1.2母线核相点:50OkV同步向量测量屏同相位测试:紫青1号线A相为基准2号主变500kV侧500kV1母线500kV2母线备注0:00紫青1号线PT端子箱相另IJ计量(V)测量、保护I(V)保护2(V)开口三角(V)A-N61.961.961.7107.9B-N61.861.861.8107.5C-N61.961.961.9101.92号主变SOOkV便PT段子箱相别计量(V)测量、保护I(V)保护2(V)开口三角(V)A-
2、N61.962.061.9107.4B-N61.761.861.8107.5C-N61.962.062.0107.8500kV1母线PT端子箱相别计量(V)测量、保护1(V)保护2(V)A-N62.062.062.0SOOkV2母线PT端子箱相别计量(V)测量、保护1(V)保护2(V)A-N61.662.162.1紫青1号线电压装置采样相别电度表(V)线路保护A(V)线路保护B(V)5023断路器保护A(V)A-N61.8161.9661.6762.04B-N62.0162.2061.7462.14C-N62.0761.8361.7862.23相别5023断路器保护B(V)5022断路器保护A
3、(V)5022断路器保护B(V)5023断路器测控(V)A-N61.5762.0061.6161.875B-N61.7362.0961.6661.994C-N61.8562.2761.7462.109相另IJ5022断路器测控(V)PMU(V)故障录波A(V)故障录波B(V)A-N61.90061.83361.76461.704B-N61.97161.93061.81261.880C-N61.98162.02061.88061.9822号主变SOOkV侧电压装置采样相别电度表(V)主变保护A(V)主变保护B(V)5022断路器保护A(V)A-N61.7962.04561.63261.90B-N
4、61.9662.19361.73262.09C-N62.1262.36961.83262.19相别5022断路器保护B(V)5021断路器保护A(V)5021断路器保护B(V)5022断路器测控(V)A-N61.3862.0961.6861.909B-N61.7662.1361.7262.052C-N61.7462.1761.8662.136相别5021断路器测控(V)PMU(V)故障录波A(V)故障录波B(V)A-N61.90961.86161.70461.649B-N61.99061.97861.80661.821C-N62.20762.12661.97861.96250OkV1母线电压装
5、置采样相另IJ5011断路器保护A(V)5011断路器保护B(V)5021断路器保护A(V)5021断路器保护B(V)A-N62.0061.6362.1061.69相别5011断路器测控(V)5021断路器测控(V)PMU(V)故障录波(V)A-N61.96261.96461.96061.763500kV2母线电压装置采样相别5012断路器保护A(V)5012断路器保护B(V)5023断路器保护A(V)5023断路器保护B(V)A-N62.1661.7362.1661.73相另IJ5012断路器测控(V)5023断路器测控(V)PMU(V)故隙录波(V)A-N60.99361.98861.93
6、761.842第二次核相:1号主变50OkV侧、1号主变22OkV侧、66kV1母线、22OkV1、2、3、4母线核相点1:主变故障录波屏同相位测试:1号主变50OkV侧A相为基准1号主变220kV侧66kV1母线2号主变500kV侧备注Oz00核相点2:1号主变测同相位测试:1号主变控屏220kV侧A相为基准220kV1母线220kV2母线备注0O0核相点3:22OkV1、3母分段保护测控屏同相位测试:22OkV1母线A相为基准220kV3母线备注0核相点4:220kV2小室电压并列屏同相位测试:220kV3母线A相为基准220kV4母线备注01号主变500kV侧PT端子箱相别计量(V)测量
7、、保护I(V)保护2(V)开口三角(V)A-N62.962.762.7108.4B-N61.861.861.8108.3C-N61.962.062.0108.51号主变220kVftPT端子箱相别计量(V)测量、保护I(V)保护2(V)开口三角(V)A-N62.862.862.7109.0B-N61.861.861.8109.3C-N61.861.861.8109.566kV1母PT端子箱相另IJ计量(V)测量、保护I(V)保护2(V)开口三角(V)A-N59.860.059.935.5B-N59.259.259.235.5C-N58.858.858.835.3220kV1母PT端子箱相另IJ
8、计量(V)测量、保护I(V)保护2(V)开口三角(V)A-N62.662.662.6109.3B-N61.861.861.7108.2C-N61.761.861.7109.3220kV2母PT端子箱相别计量(V)测量、保护I(V)保护2(V)开口三角(V)A-N62.862.860.6109.4B-N61.861.861.8109.4C-N61.861.861.8109.8220kV3母PT端子箱相别计量(V)测量、保护I(V)保护2(V)开口三角(V)A-N62.662.662.3109.0B-N61.361.661.6109.2C-N61.761.661.7109.4220kV4母PT端子
9、箱相别计量(V)测量、保护I(V)保护2(V)开口三角(V)A-N62.662.662.6109.0B-N61.761.761.7109.2C-N61.761.761.7109.31号主变500kVW电压装置采样相另IJ电度表(V)主变保护A(V)主变保护B(V)5011断路器保护A(V)A-N61.8962.19961.60662.17B-N61.9362,24461.63562.09C-N62.0662,34161.70662.17相别5011断路器保护B(V)5012断路器保护A(V)5012断路器保护B(V)5011断路器测控(V)A-N61.7662.2361.2461.877B-N
10、61.7262.1961.8161.871C-N61.8162.1861.8061.880相别5012断路器测控(V)PMU(V)故障录波(V)A-N61.87861.99961.931B-N61.87161.95061.890C-N61.88062.02761.9761号主变220kV侧电压装置采样相别电度表(V)主变保护A(V)主变保护B(V)220kV侧测控(V)A-N61.8962.03461.44861.825B-N61.8362.13961.58961.869C-N62.0362.17661.66161.946相另IJPMU(V)故隙录波(V)A-N61.76861.699B-N6
11、1.88661.818C-N61.97161.88766kV1母线电压装置采样相别1号主变66kV电度表(V)1号电容器电度表(V)2号电容器电度表(V)1号电抗器电度表(V)A-N59.0259.059.059.0B-N59.3759.459.359.4C-N59.0559.159.059.0相别1号站用变电度1号SVG变压器母线测控(V)1号主变66kV测表(V)电度表(V)控(V)A-N58.959.059.08759.119B-N59.459.459.50259.440C-N59.159.059.17959.153相别1号电容器测控(V)2号电容器测控(V)1号电抗器测控(V)1号站用
12、变测控(V)A-NB-NC-N相别1号SVG变压器66kV测控(V)主变保护A(V)主变保护B(V)母线保护(V)A-N59.06659.24459.81059.749B-N59.43559.52859.70459.116C-N59.13159.26759.89759.764相别1号电容器保护(V)2号电容器保护(V)1号电抗器保护(V)1号站用变保护(V)A-N59.93359.99959.64759.052B-N5931659.34959.41659.423C-N59.97959.08959.11059.097相别1号SVG变压器保护A(V)1号SVG变压器保护B(V)故障录波A(V)故障录波B(V)A-N59.34759.80959.99959.984B-N59.73259.1765937959358C-N59