《塔式起重机电气与避雷一般规定.docx》由会员分享,可在线阅读,更多相关《塔式起重机电气与避雷一般规定.docx(2页珍藏版)》请在第一文库网上搜索。
1、塔式起重机电气与避雷一般规定(最新版)编制人:审核人:审批人:编制单位:编制时间:一年月日序言下载提示:该文档是本店铺精心编制而成的,希望大家下载后,能够帮助大家解决实际问题。文档下载后可定制修改,请根据实际需要进行调整和使用,谢谢!并且,本店铺为大家提供各种类型的安全管理制度,如通用安全、交通运输、矿山安全、石油化工、建筑安全、机械安全、电力安全、其他安全等等制度,想了解不同制度格式和写法,敬请关注!Download tips: This document is carefully compiled by this editor. I hope that afteryou download
2、it, it can help you solve practical problems. The document can becustomized and modified after downloading, please adjust and use it according to actualneeds, thank you!In addition, this shop provides you with various types of safety management systems,such as general safety, transportation, mine sa
3、fety, petrochemical, construction safety,machinery safety, electrical safety, other safety, etc. systems, I want to know the formatand writing of different systems ,stay tuned!塔式起重机电气与避雷一般规定1、塔式起重机的金属结构、轨道、所有电气设备的金属外壳、金属线管等均应可靠接地,接地电阻不大于4Q,重复接地电阻不大于10Q。2、塔式起重机的电气系统应按要求设置短路和过电流、失压及零位保护、错相与缺相保护。切断总电源的
4、紧急开关,应符合要求。在塔式起重机安装、维修、调整和使用中不得任意改变电路。3、电气系统对地的绝缘电阻不小于0.5MQ。4、塔机安装位置应避开架空输电线路。当不能避开时,塔机上任何部位与架空输电线路应保持安全距离,安全距离应符合表4规定;安全距离达不到表中规定时,必须采取绝缘隔离防护措施,并应悬挂醒目的警告标志。表4塔式起重机任何部位与辘电线间的安全距离11035110220330500沿垂直方向1.53.04.05.06.07.08.5沿水平方向1.52.03.54.06.07.08.55、避雷针高度应为12m,引下线宜采用铜导线单独铺设并保证电气连接,导线截面应不小于16mm2o6、避雷接地装置应符合施工现场临时用电技术规范JGJ46的规定。