《污水厂室内强制通风设备技术参数规范.docx》由会员分享,可在线阅读,更多相关《污水厂室内强制通风设备技术参数规范.docx(4页珍藏版)》请在第一文库网上搜索。
1、污水厂室内强制通风设备技术规范1概述通风设备在污水处理厂中主要安装于室内强制通风;2供货范围通风设备应包括风机、风管、控制箱以及有效和安全运行所必需的附件。3设备清单及技术参数A.风机序号名称规格安装位置数量3-17低噪音壁式轴流风机DFBZNo.2.51=800m3h,H=42Pa,n=1450rpm,N=O.025kW(220V),58dB(A),G=15kg风机出风口自带45防雨弯头。细格栅及旋流沉砂池17-13低噪音壁式轴流风机DFBZNo.2.51=800m3h,H=42Pa,n=1450rpm,N=O.025kW(220V),58dB(A),G=16kg,60%风机出风口自带45防
2、雨弯头。接触消毒池及回用水泵房17-14低噪音壁式轴流风机DFBZNo.3.21=1940m3h,H=62Pa,n=1450rpm,N=O.06kW(220V),62dB(A),G=19kg,60%风机出风口自带45防雨弯头。29-24低噪音壁式轴流风机DFBZNo.51=6920m3h,H=142Pa,n=1450rpm,N=O.037kW(380V),66dB(),G=40kg,60%风机出风口自带45防雨弯头。污泥储池及脱水机房49-25低噪音壁式轴流风机DFBZNo.2.51=600m3h,H=40Pa,n=1450rpm,N=O.025kW(220V),57dB(A),G=15kg,
3、n260%风机出风口自带45防雨弯头。19-26低噪音壁式轴流风机DFBZNo.3.21=1940m3h,H=62Pa,n=1450rpm,N=O.06kW(220V),62dB(A),G=19kg,60%风机出风口自带45防雨弯头。110-11低噪音壁式轴流风机DFBZNo.2.51=600m3h,H=40Pa,n=1450rpm,N=O.025kW(220V),57dB(A),G=15kg,60%风机出风口自带45防雨弯头。鼓风机房、变配电间及机修车间110-12低噪音壁式轴流风机1=6920m3h,H=142Pa,7DFBZNo.5n=1450rpm,N=O.037kW(380V),66
4、dB(A),G=40kg,60%风机出风口自带45防雨弯头。10-13低噪音壁式轴流风机DFBZNo.3.61=2480m3h,H=73Pa,n=1450rpm,N=O.09kW(220V),63dB(A),G=22kg,60%风机出风口自带45防雨弯头。511-4-1低噪音壁式轴流防腐风机DFBZNo.3.21=1940m3h,H=62Pa,n=1450rpm,N=O.06kW(380V),62dB(),G=19kg,60%风机出风口自带45防雨弯头。加氯加药间411-4-2低噪音壁式轴流防腐风机DFBZNo.2.51=1000m3h,H=54Pa,n=1450rpm,N=O.04kW(38
5、0V),58dB(A),G=15kg,n260%风机出风口自带45防雨弯头。411-4-3低噪音壁式轴流防腐、防爆风机DFBZNo.3.21=1940m3h,H=62Pa,n=1450rpm,N=O.06kW(380V),62dB(A),G=19kg,60%风机出风口自带45防雨弯头。411-4-4低噪音壁式轴流防腐、防爆风机DFBZNo.2.51=1000m3h,H=54Pa,n=1450rpm,N=O.04kW(380V),58dB(A),G=15kg,n60%风机出风口自带45防雨弯头。411-4-5低噪音壁式轴流防腐、防爆风机DFBZNo.3.61=2480m3h,H=73Pa,n=1
6、450rpm,N=O.09kW(220V),63dB(A),G=22kg,n260%风机出风口自带45防雨弯头。211-4-6低噪音壁式轴流风机DFBZNo.3.21=1940m3h,H=62Pa,n=1450rpm,N=O.06kW(220V),62dB(A),G=19kg,60%风机出风口自带45防雨弯头。113-25吸顶式房间通风器B1D15-451=500m3h,H=260Pa,n=1450rpm,N=O.09kW(220V),48dB(A),60%(自带止回阀)生产调度中心913-26低噪音壁式轴流风机DFBZNo.2.51=1000m3h,H=54Pa,n=1450rpm,N=O.
7、04kW(380V),58dB(A),G=15kg,60%风机出风口自带45防雨弯头。413-27低噪音壁式轴流风机DFBZNo.3.21=1940m3h,H=62Pa,n=1450rpm,N=O.06kW(220V),62dB(A),G=19kg,n260%风机出风口自带45防雨弯头。113-28低噪音壁式防爆轴流风机DFBZNo.3.21=1940m3h,H=62Pa,n=1450rpm,N=O.06kW(380V),262dB(A),G=19kg,n60%风机出风口自带45防雨弯头。B.空调序号名称规格安装位置数量3-18KFR501W/(505961)NhAaD-3柜机Qc=5.23k
8、W,Qh=5.8IkW,N=1.4kW,EER=3.5室内机:1=1010m3h,33dB(A),G=37kg室外机:53dB(A),G=47kg细格栅及旋流沉砂池17-15KFR501W/(505961)NhAaD-3柜机Qc=5.23kW,Qh=5.8IkW,N=14kW,EER=3.5室内机:1=1010m3h,33dB(A),G=37kg室外机:53dB(A),G=47kg接触消毒池及回用水泵房110-14KFR501W/(505961)NhAaD-3柜机Qc=5.23kW,Qh=5.8IkW,N=1.4kW,EER=3.5室内机:1=1010m3h,33dB(A),G=37kg室外机
9、:53dB(A),G=47kg鼓风机房、变配电间及机修车间110-15KFR-721W/(72591)FNhAaDH柜机Qc=7.2kW,Qh=8.9kW,N=2.HkW,EER=3.4室内机:1=1200m3h,22dB(A),G=42kg室外机:56dB(A),G=51kg413-29KF-35GW/(35392)NhAaD-3挂机Qc=3.5kW,Qh=3.75kW,N=0.95kW,EER=3.6室内机:1=630m3h,42dB(),G=IOkg室外机:50dB(A),G=32kg生产调度中心613-30KFR501W/(505961)NhAaD-3柜机Qc=5.23kW,Qh=5.
10、8IkW,N=1.4kW,EER=3.5室内机:1=1010m3h,33dB(A),G=37kg室外机:53dB(A),G=47kg1813-31KFR-721W/(72591)FNhAaDT柜机Qc=7.2kW,Qh=8.9kW,N=2.I1kW,EER=3.4室内机:1=1200m3h,22dB(A),G=42kg室外机:56dB(A),G=51kg64技术要求通风机应采用直联驱动形式的轴流风机,通风机应具有高效、节能、防腐蚀、低噪声、长寿命,免维护结构;叶片应采用高效率的机翼型叶片,可选用PAGAS:抗静电玻璃纤维增强聚酰胺材质,进行普通送排风,抗腐蚀排风,防爆送排风;叶轮应采用高分子或铝制叶轮,达到G2.5平衡等级。电机应采用优质品牌,电机防护等级不低于IP55,温升B级,绝缘等级F及以上。电机应当能得到充分冷却。防爆电机可选:隔爆型,隔爆等级达到ExdIIBT4,防护等级IP55,温升B级,绝缘等级F级;通风机应采用低噪音的结构形式,开机时噪音不大于70dB(A);5设备安装与检验试运转时风机应无叶轮摩擦碰撞等异常声响。安装后,供应商应负责进行2小时空载实验,以证明其运行的稳定性。